Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

6.2.3

High Efficiency Mode

When the UPS is operating in High Efficiency mode, the bypass source supplies

the commercial AC power to the load directly.
Figure 6---4 shows the path of electrical power through the UPS system when

operating in High Efficiency mode.

CB1

CB2

K1

K5

K3

K2

Open

Closed

Breakers Contactors

Main Power Flow

Energized

De--Energized

Trickle Current

RECTIFIER

BOOST

CONVERTER

INVERTER

HIGH EFFICIENCY MODE

CHARGER

BATTERY

STATIC

SWITCH

MAINTENANCE

BYPASS SWITCH

MAINTENANCE

BYPASS SWITCH

Figure 6---4. Path of Current Through the UPS in High Efficiency Mode

In High Efficiency mode, the output of the system is provided with three phase AC

power directly from the system bypass input. Some power line filtering and spike

protection is provided to the load but no active power conditioning or battery

support is available to the output of the system in the High Efficiency mode of

operation. However if the bypass source falls outside of a predetermined voltage

or frequency window, the system forward transfers and the inverter assumes the

load. The transfer takes place in less than 4 ms (quarter cycle), to ensure loads

being fed by the system output are not interrupted.
The internal bypass is comprised of a solid state silicon controlled rectifier (SCR)

static switch (SSW), and a back feed protection contactor (K5). The static switch is

rated as a continuous duty device. The static switch is wired in series with the back

feed protection contactor and together they are wired in parallel with the inverter.
In the High Efficiency mode, the static switch is turned on to supply the majority of

the load current directly to the load while the Inverter remains on line, ready to

assume suppling the load.
High Efficiency mode is a normal operating mode, and not an alarm condition.

While the UPS is in High Efficiency mode, the

NORMAL light on the front display

will illuminate.