3 ups standard features, 2 ups circuit breakers, 3 smart load off – Powerware 9330 User Manual

Page 92: 4 maintenance bypass switch, 5 cold start switch, 1 customer interface

Advertising
background image

7--4

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

7.2.2 UPS Circuit Breakers

The UPS can contain as many as 10 circuit breakers, depending on the system

options. The UPS circuit breakers are described in detail in Chapter 9, “UPS

Operating Instructions.”

UPS Cabinet

CB1 controls the input to the UPS rectifier, while CB2 controls the battery input to the

UPS inverter. CB1 and CB2 are manually controlled.

Optional Battery Cabinet

A local battery circuit breaker controls the output of each battery cabinet, providing

the ability to service each battery string individually.

Optional Options Cabinet

Input, output, and bypass circuit breakers control the flow of current to and from the

installed transformers.

7.2.3 Smart LOAD OFF

A smart

LOAD OFF pushbutton is provided for situations where you must quickly

control the UPS output. The pushbutton is located on the front of the UPS for

quick access, but provides a safety feature to prevent inadvertent load dumps. The

LOAD OFF pushbutton is described in detail in Chapter 9, “UPS Operating

Instructions.”

7.2.4 Maintenance Bypass Switch

An internal Maintenance Bypass switch is provided to completely isolate the main

power processing unit of the UPS during service. The

Maintenance Bypass

Switch is described in detail in Chapter 9, “UPS Operating Instructions.”

7.2.5 Cold Start Switch

A Cold Start switch is provided to start the UPS in Battery Mode when no

commercial power is available. The

Cold Start Switch is described in detail in

Chapter 9, “UPS Operating Instructions.”

7.3

UPS Standard Features

The UPS has many standard features that provide cost-effective and consistently

reliable power protection:

7.3.1 Customer Interface

Computer Interface

One serial communications port is standard on all units, and is electrically isolated

from the UPS. You can use this ports to link the UPS to the features described in

Chapter 12,

Serial Communicationsand Chapter 13, “Remote Notification.”

Building Alarm Monitoring

You can connect your facility’s alarm system contacts to four (4) inputs in the UPS.

The UPS uses these inputs to monitor your building alarms in addition to the UPS

status. This feature is described further in Chapter 10, “Using Features and Options.”

Advertising