Powerware 9330 User Manual

Page 132

Advertising
background image

11--4

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

ALARMS

Message

Indication

Log

Relay

Phone

Horn

Input Phase Rotation

1

No

1

HA User Action Required

Input Phase Rotation OK

Off

No

1

HA Condition Cleared

Inverter DC Link OV

1

No

1

HA Service Required

Inverter DC Link OV OK

Off

No

1

HA Condition Cleared

Inverter DC Link UV

1

No

1

HA Service Required

Inverter DC Link UV OK

Off

No

1

HA Condition Cleared

Inverter Not Responding

2

No

1

HA Service Required

Inverter Not Responding OK

Off

No

1

HA Condition Cleared

Inverter Overheating Shutdown

1

No

1

HA User Action Required

Inverter Overheating Shutdown OK

Off

No

1

HA Condition Cleared

Inverter Overheating Warning

1

No

1

HA Shutdown Imminent

Inverter Overheating Warning OK

Off

No

1

HA Condition Cleared

Inverter Overload

1

No

1

HA User Action Required

Inverter Setup Required

1

No

1

A

Service Required

Inverter Tripped

1

No

1

A

User Action Required

Inverter Voltage Failure

1

4

1

HA Service Required

Inverter Voltage Failure OK

Off

No

1

HA Condition Cleared

Load Over 100%

1

No

1

HA Shutdown Imminent

Load Over 100% OK

Off

No

1

HA Condition Cleared

Load Over 125%

1

No

1

HA Shutdown Imminent

Load Over 125% OK

Off

No

1

HA Condition Cleared

MCU Not Responding

1

No

1

HA Service Required

MCU Not Responding OK

Off

No

1

HA Condition Cleared

Not Enough UPMs

1

No

1

HA User Action Required

Not Enough UPMs OK

Off

No

1

HA Condition Cleared

Output Overload 100%

1

No

1

HA User Action Required

Output Overload 100% OK

Off

No

1

HA Condition Cleared

Output Overload 125%

1

No

1

HA User Action Required

Output Overload 125% OK

Off

No

1

HA Condition Cleared

Output Phase Rotation

1

No

1

HA User Action Required

Output Phase Rotation OK

Off

No

1

HA Condition Cleared

Parallel Setup Error

1

4

1

A

Service Required

Parallel Setup Error OK

Off

No

1

A

Condition Cleared

Power Board Sensing Failed 1

1

4

1

HA Service Required

Power Board Sensing Failed 1 OK

Off

No

1

HA Condition Cleared

Rectifier Configuration Failure

1

No

1

HA User Action Required

Rectifier Configuration Failure OK

Off

No

1

HA Condition Cleared

Rectifier Over Voltage

1

No

1

HA Service Required

Rectifier Over Voltage OK

Off

No

1

HA Condition Cleared

Advertising