3--6

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

3.

Remove screws securing internal safety shield panels and remove panels to

gain access to batteries.

4.

Connect the string of battery trays together by mating the loose red connector

from each tray to the fixed black connector mounted on the front edge of the

tray above it (see Figures 3---1 and 3---3 or 3---2 and 3---3).

5.

Connect the pigtail battery connectors at the top battery trays as shown in

Figure 3---3.

6.

Secure the UPS by reinstalling safety shield panels, front vented panels, and

left front solid panel.

3.4.2 Electrically Connecting Battery Cabinet Battery

Strings

The battery cabinets are shipped with each internal battery connection string

electrically disconnected. Connect the battery strings in accordance with the

following procedure:

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE STEPS IN

THIS SECTION.

1.

Ensure that battery breaker is in the OFF position. If not, set breaker to OFF

position.

2.

Remove the front vented panel from battery cabinet. The front panel is

secured with magnetic latches and is removed by pulling panel straight

forward to disengage magnetic latches.

3.

Remove screws securing internal safety shield panel and remove panel to gain

access to batteries.

4.

Connect the string of battery trays together by mating the loose red connector

from each tray to the fixed black connector mounted on the front edge of the

tray above it (see Figure 3---3).

5.

Connect the pigtail battery connectors at the top battery trays as shown in

Figure 3---3.

6.

Secure the Battery Cabinet by reinstalling safety shield panel, and front vented

panel.

7.

If you are installing more than one battery cabinet, perform Steps 1 through 6

for each cabinet.