POWER WIRING INSTALLATION NOTES

164201300---1

A---16

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table U. Power Cable Conduit Requirements Powerware 9330 (35 kVA--40 kVA)

Powerware

System

Voltage

Terminal

Number of

Wires in

Conduit

Minimum

Conduit

Trade Size

(inches)

Number of

Conduits

AC Input to UPS

(A, B, C, Gnd)

4

1-1/4

1

9330-40/35

208

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2

1

AC

Output

(A, B, C, Neut, Gnd)

5

2

1

AC Input to UPS

(A, B, C, Gnd)

4

1

1

9330---40/35

480

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

1

1

C

Output

(A, B, C, Neut, Gnd)

5

1

1

AC Input to UPS

(A, B, C, Gnd)

4

3/4

1

9330---40/35

600

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

3/4

1

C

Output

(A, B, C, Neut, Gnd)

N/A

N/A

N/A

9330---40/35

288

DC

External Battery DC Source

(Positive, Negative, Gnd)

3

1

1

AC Input to UPS

(A, B, C, Gnd)

4

1-1/2

1

9330-40/40

208

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2

1

C

Output

(A, B, C, Neut, Gnd)

5

2

1

AC Input to UPS

(A, B, C, Gnd)

4

3/4

1

9330-40/40

480

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

1

1

C

Output

(A, B, C, Neut, Gnd)

5

1

1

AC Input to UPS

(A, B, C, Gnd)

4

3/4

1

9330-40/40

600

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

3/4

1

C

Output

(A, B, C, Neut, Gnd)

N/A

N/A

N/A

9330---40/40

288

DC

External Battery DC Source

(Positive, Negative, Gnd)

3

1-1/4

1