3.2 Battery Type

The following battery types are supplied in the UPS Cabinets and external Battery

Cabinets. When purchasing UPS Cabinets or external Battery Cabinets without

batteries, only the following types are recommended. Use of any other battery type

inside Powerware cabinets will void the product warranty.

Battery Manufacturer

Yuasa, Inc.

Powersonic/Enersys

Battery Model

NPX–100R or NPX–100B 12GAX105

Battery Quantity

Powerware 9330 (10 kVA---20 kVA)

Powerware 9330 (25 kVA---40 kVA)

24

48

24

48

3.3 Battery Installation

3.3.1 Installing Internal Batteries in the UPS Cabinet

If the UPS cabinet was ordered without batteries, install the batteries in accordance

with the following procedure.

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE STEPS IN

THIS SECTION.

1.

Ensure that battery breaker CB2 is in the OFF position. If not, set breaker to

OFF position.

2.

Remove left front solid panel and right front vented panel from Powerware 9330

(10 kVA---20 kVA) UPS or left front solid panel and front vented panels from

Powerware 9330 (25 kVA---40 kVA) UPS. Front panels are secured with

magnetic latches and are removed by pulling panels straight forward to

disengage magnetic latches.

3.

Remove screws securing internal safety shield panels and remove panels to

gain access to battery trays.

4.

Remove battery trays, containing wiring and nylon straps, from the UPS

cabinet.

5.

Select batteries in a accordance with paragraph 3.2. Use batteries of the same

age, type, and manufacturer, in each string, so UPS performance is not

affected.

6.

Install four batteries per tray and electrically interconnect the batteries in

accordance with Figure 3---1 or 3---2.

7.

Secure batteries to tray using nylon straps.

8.

Reinstall battery trays into the UPS cabinet.

9.

Connect battery strings in accordance with paragraph 3.4.1.