Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

6.2.1

Normal Mode

Figure 6---2 shows the path of electrical power through the UPS system when the

UPS is operating in Normal mode.

CB1

CB2

K1

K5

K3

K2

Open

Closed

Breakers Contactors

Main Power Flow

Energized

De--Energized

Trickle Current

RECTIFIER

STATIC

SWITCH

BOOST

CONVERTER

INVERTER

NORMAL MODE

CHARGER

BATTERY

MAINTENANCE

BYPASS SWITCH

MAINTENANCE

BYPASS SWITCH

Figure 6---2. Path of Current Through the UPS in Normal Mode

During normal UPS operation, power for the system is derived from a utility input

source through the input breaker CB1 and contactor K1. ”Normal” appears on the

front panel and indicates the incoming power is within voltage and frequency

acceptance windows. Three phase AC input power is converted to DC using a

full---wave, six---pulse, solid---state rectifier block which supplies unregulated DC

voltage to a boost converter which in turn supplies a higher and regulated DC

voltage to the inverter. The battery is not charged directly from the unregulated

rectifier. Instead, a separate battery charger is used to maintain the proper charge

level on the battery during normal operation.