DESCRIPTION:

DATE:

DRAWING NO:

4 of 17

SHEET:

REVISION: E

NOTE:

Callout letter

and

map to drawing #164201300---6

,

, ,

071501

164201300---1

POWER WIRING INSTALLATION NOTES

D

D

A---5

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table E. Ratings & External Wiring Requirements for

Powerware 9330 (10 kVA---20 kVA)

Options Cabinet OUTPUT Transformer

Ratings 50/60 Hz

Basic unit ratings at

Voltage

Output

Conductor

g

0.7 lagging PF load

Series/

Model

kVA/KW

Input

Output

Output

Current

(Amps)

Minimum

Size

20/10

9.5/6.65

208

208

26.4

10

AC Output from

20/10

9.5/6.65

208

480

11.4

14

AC

OUTPUT

AC Output from

Output Transformer

to Critical Load

20/15

14.25/10

208

208

39.6

8

OUTPUT to Critical Load

(0.95min.PF)

20/15

14.25/10

208

480

17

12

(0.95min.PF)

3 , 1 Neutral, 1 gnd

20/20

19/13.3

208

208

52.7

6

g

20/20

19/13.3

208

480

22.8

10

Table F. Ratings & External Wiring Requirements for

Powerware 9330 (10 kVA---20 kVA)

Options Cabinet OUTPUT Without Output Transformer

Ratings 50/60 Hz

Basic unit ratings at

Voltage

Output

Conductor

g

0.7 lagging PF load

Series/

Model

kVA/KW

Input

Output

Output

Current

(Amps)

Minimum

Size

AC

AC Output from Output

20/10

10/7

208

208

27.8

8

AC

OUTPUT

p

p

to Critical Load

(0 95min PF)

20/15

15/10.5

208

208

41.6

6

(0.95min.PF)

3 , 1 Neutral, 1 gnd

20/20

20/14

208

208

55.5

4