Figure 6 . main elements of the ups system – Powerware 9330 User Manual

Page 76

Advertising
background image

6--2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

DIGITAL

AC INPUT TO

AC INPUT TO

AC OUTPUT

INPUT

RECTIFIER

INVERTER

FILTER

METERING

RECTIFIER/

BYPASS

TO CRITICAL

STATIC

SWITCH

CHARGER

LOAD

OUTPUT

FILTER

INPUT

BATTERY

BREAKER

CB2

BREAKER

CB1

POWER PROCESSING UNIT

UPS CABINET

INPUT

CONTACTOR

BATTERY

CONVERTER

DC--DC

OUTPUT

CONTACTOR

BATTERY

SWITCHES

BATTERY

CHARGER

CONTACTOR

BACKFEED

PROTECTION

K1

K3

K5

MAINTENANCE

BYPASS SWITCH

BOOST

Figure 6---1. Main Elements of the UPS System

If utility power is interrupted or falls outside the parameters specified in Chapter 15,

“Product Specifications,” the UPS uses a

backup battery supply to maintain power

to the critical load for a specified period of time or until the utility power returns.

For extended power outages, the UPS allows you to either transfer to an alternative

power system (such as a generator) or shut down your critical load in an orderly

manner.
The emergency bypass consist of a continuous duty static switch, and backfeed

protection contactor (K5). The backfeed protection contactor is located in series

with the static switch. For manual transfers to bypass, the static switch is also

used. The static switch is armed and ready during both types of transfers.
A wraparound Maintenance Bypass switch provides a means of isolating the UPS

Power Processsing Unit (PPU) for servicing, while still suppling power to the critical

load.
The operation of the UPS system is described in greater detail in the following

paragraphs.