15--1

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Product Specifications

15.1

Model Numbers

The UPS systems are housed in freestanding, cabinets with safety shields behind

the front panels. The UPS systems are available in 50/60 Hz with various output

power ratings. Smaller models within a system may be upgraded in the field to

larger models:

System

Models

Nominal Frequency

Powerware 9330

10, 15, 20

kVA

50/60 Hz

Powerware 9330

25, 30, 35, 40

kVA

50/60 Hz

The following sections detail the input, output, environmental, and battery specifications for

the UPS.

15.2

UPS System Input

Operating Input

Voltage

(Nominal +10/--15%)

600 VAC for operation from 510 VAC to 660 VAC (50/60 Hz)

480 VAC for operation from 408 VAC to 528 VAC (50/60 Hz)

208 VAC for operation from 177 VAC to 229 VAC (50/60 Hz)

Operating Input

Frequency Range

3 Hz of nominal (50 Hz or 60 Hz)

Operating Input

Current

Refer to Appendix A, Tables A through F, for 10, 15, and 20 kVA

Models and Tables G through M, for 25, 30, 35, and 40 kVA

Models.

Reduced for Generator:

Adjustable

Battery Charge

Current

Battery Charge:

Up to 7 Amperes for 10, 15, and 20 kVA models

Up to 14 Amperes for 25, 30, 35, and 40 kVA models

Input Current

Harmonic Content

10% THD at full load (with input filter option installed)

30% THD at full load (without input filter option installed)

Power Factor

Minimum 0.96

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4

Battery Voltage

288 VDC nominal

(144 cells @2V/cell)

15