4 connecting batteries, 1 electrically connecting integral battery strings – Powerware 9330 User Manual

Page 61

Advertising
background image

3--5

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

3.3.2 Installing Internal Batteries in the Battery Cabinet

If the battery cabinet was ordered without batteries, install the batteries in

accordance with the following procedure.

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE STEPS IN

THIS SECTION.

1.

Ensure that battery breaker is in the OFF position. If not, set breaker to OFF

position.

2.

Remove front vented panel from battery cabinet. The front panel is secured

with magnetic latches and is removed by pulling panel straight forward to

disengage magnetic latches.

3.

Remove screws securing internal safety shield panel and remove panel to gain

access to battery trays.

4.

Remove battery trays, containing wiring and nylon straps, from the UPS

cabinet.

5.

Select batteries in a accordance with paragraph 3.2. Use batteries of the same

age, type, and manufacturer, in each string, so UPS performance is not

affected.

6.

Install four batteries per tray and electrically interconnect the batteries in

accordance with Figure 3---1.

7.

Secure batteries to tray using nylon straps.

8.

Reinstall battery trays into the UPS cabinet.

9.

Connect battery strings in accordance with paragraph 3.4.2.

3.4 Connecting Batteries

3.4.1 Electrically Connecting Integral Battery Strings

The UPS cabinet is shipped with each internal battery connection string electrically

disconnected. Connect the battery strings in accordance with the following

procedure:

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE STEPS IN

THIS SECTION.

1.

Ensure that battery breaker CB2 is in the OFF position. If not, set breaker to

OFF position.

2.

Remove left front solid panel and right front vented panel from Powerware 9330

(10 kVA---20 kVA) UPS or left front solid panel and front vented panels from

Powerware 9330 (25 kVA---40 kVA) UPS. Front panels are secured with

magnetic latches and are removed by pulling panels straight forward to

disengage magnetic latches.