11 ups and critical load shutdown, 12 ups maintenance bypass transfer – Powerware 9330 User Manual

Page 121

Advertising
background image

9--7

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

9.10 Transfer from Normal to Bypass Mode with UPS

Shutdown

1.

Transfer critical load to bypass by performing procedure in paragraph 9.6.

2.

Press the System Control pushbutton. The System Control screen appears.

3.

Toggle

PPU OFF from the System Control menu.

The PPU status indicates SHUTDOWN.

The input, output, and battery contactors

open and the PPU is turned off. The bypass source supplies the critical load.

WARNING:

Power is present inside the UPS and Options cabinets

.

9.11 UPS and Critical Load Shutdown

To perform maintenance or service on the critical load, shut down power to the

load by performing the following procedure:

1.

Turn off all equipment that is being powered by the UPS.

2.

Perform

LOAD OFF procedure contained in paragraph 9.15.1

The input, output, battery and bypass backfeed contactors open and the PPU is

turned off.

3.

On the UPS, open Input circuit breaker CB1.

4.

On the UPS, open Battery circuit breaker CB2.

5.

If installed, open the Battery breakers on Battery cabinets.

6.

If Options cabinet is installed, open Options cabinet Input, Bypass, and Output

circuit breakers.

WARNING:

Power is present inside the Options cabinet, until

the upstream input feeder

circuit breaker is opened. Power is present inside the UPS cabinet due

to internal batteries.

7.

Open the UPS input and bypass (if dual feed) feeder circuit breakers.

9.12 UPS Maintenance Bypass Transfer

To transfer the critical load to Maintenance Bypass, perform the following

procedure:

1.

Transfer critical load to bypass by performing procedure in paragraph 9.6.

2.

Manually set the UPS Maintenance Bypass Switch to

BYPASS, by turning

slowly through the

TEST position to BYPASS.

The input, output, battery and bypass backfeed contactors open and the PPU is

turned off. The maintenance bypass source supplies the critical load.

WARNING:

Power is present inside the UPS and Options cabinets

.