POWER WIRING INSTALLATION NOTES

164201300---1

A---13

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

10.

Per NEC article 300-20(a), all three phase conductors must be run in the same conduit.

Neutral and ground must be run in the same conduit as the phase conductors.

11.

Conduit is sized to accommodate one neutral conductor the same size as the phase

conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized

neutral conductor are to be installed, check the size of the conduit needed to

accommodate the extra wire or size and use that conduit size in place of the conduit size

listed in table R. All 9330 products can accommodate a double size neutral.

12.

Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW,

THHW, THW-2.

Table R. Power Cable Conduit Requirements Powerware 9330 (10 kVA--15 kVA)

Powerware

System

Voltage

Terminal

Number of

Wires in

Conduit

Minimum

Conduit

Trade Size

(inches)

Number of

Conduits

AC Input to UPS

(A, B, C, Gnd)

4

1/2

1

9330-20/10

208

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

3/4

1

C

Output

(A, B, C, Neut, Gnd)

5

3/4

1

AC Input to UPS

(A, B, C, Gnd)

4

1/2

1

9330---20/10

480/600

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

1/2

1

C

Output

(A, B, C, Neut, Gnd)

5

1/2

1

9330---20/10

288

DC

External Battery DC Source

(Positive, Negative, Gnd)

3

1/2

1

208/480

AC Input to UPS

(A, B, C, Gnd)

4

1/2

1

9330---20/15

208/480

/600

AC

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

3/4

1

AC

Output

(A, B, C, Neut, Gnd)

5

3/4

1

9330---20/15

288

DC

External Battery DC Source

(Positive, Negative, Gnd)

3

1/2

1