Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

the inverter rectifier. The static switch being an electronically controlled device can

be turned on immediately to pickup the load from the inverter while the inverter

output contactor K3 opens to isolates the inverter. The back feed protection

contactor is normally always closed ready to support the static switch unless the

bypass input source becomes unavailable.
During an outage, transfers to bypass are prohibited and for the safety of those

who may be working on the power lines upstream from the UPS, the back feed

protection contactor is opened, preventing system output voltage from bleeding

across the static switch snubber components to the bypass input source.
If the inverter is unable to support the load on the output of the system, to ensure

the load remains energized, the UPS will transfer the load to the internal bypass.

The output of the system will be transferred automatically to the internal bypass if

any of the following abnormal conditions occur on the output of the system: If the

output of the system exceeds acceptable voltage tolerances; System is

overloaded; Inverter failure. The transfer is initiated by turning on the static switch

and opening the output contactor K3. This kind of transfer is normally referred to as

a Make---Before---Break transfer. The transfer should take place in less than 4 mS

(quarter cycle) to ensure loads on the systems output are not interrupted. The

static switch remains on until either the inverter is able to support the system output

or the unit is placed into a maintenance position where repairs can be made.
If the UPS initiates its own transfer to bypass for any reason other than operator

intervention, the UPS will attempt to restart the inverter (if not running already) and

attempt a retransfer back on line to support the output of the system. Three

attempts will be made within ten minutes to bring the inverter back on---line

automatically before the UPS will lock out any further attempts. After three

attempts have been made, the UPS will remain in bypass and an alarm condition

will be enunciated. The UPS can also be transferred to bypass using the front

panel controls.
Bypass mode is a normal operating mode, and not an alarm condition. However, if

the UPS is unable to return to Normal mode following an automatic transfer to

Bypass mode, an alarm condition is recorded.