Powerware 9330 User Manual

Page 67

Advertising
background image

4--3

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table 4---1. Remote EPO Wire Terminations

From Remote

EPO Switch(s)

To Communications Server

Board TB5 in UPS Cabinet

Remarks

TB1

Use any open

Terminal

TB5---3

Twisted

wires (2)

TB2

Use any open

Terminal

TB5---4

wires (2)

14---18

gauge

Table 4---2. Remote EPO

3

TB5

4

REMOTE

EPO

SWITCH

TWISTED

WIRES (2)

UPS

(N.C.)

TB1

TB2

Remote EPO switch rating is 24 VDC, 1 Amp minimum.

NOTE: This switch must be a dedicated switch not tied into

any other circuits.

7.

If required, install ½-in. conduit and wiring from the Remote EPO switch to trip

circuitry of upstream protective devices. A separate contact block, with the

appropriate normally open or normally closed contacts, must be used for this

function. Remote EPO switch wiring must be in accordance with UL Class 1

requirements.

8.

When wiring is complete, remove cover from Remote EPO switch enclosure

bottom. Turn cover over and secure to enclosure bottom.

9.

Secure the UPS by reversing all steps taken to prepare it for Remote EPO

installation.