2 event history log – Powerware 9330 User Manual

Page 150

Advertising
background image

12--12

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

12.5.2 Event History Log

This key sequence prints the entire Event History Log of the UPS at the time the

data is requested. The printout begins with the oldest alarm entry in the queue and

ends with the most recent. Any alarms that occur while the Event History Log is

printing are included in chronological order.
The Event History Log lists up to 500 system events in chronological order with the

most recent event listed last. Figure 12---18 shows a sample Event History Log

printout.
In this mode, system events are continually logged through the serial port to the

device connected to the port.
The printed log entries contain a time and date stamp and the alarm text message.

Terminal mode uses this format for printing alarm entries:

MM DD YYYY

HH:MM:SS.hh

KYWD MESSAGE

::::

<CR> <LF>

Symbol

Description

MM

Month (2 digits)

YYYY

Year (4 digits)

DD

Day (2 digits)

HH

Hour (2 digits)

MM

Minute (2 digits)

SS

Second (2 digits)

hh

Hundredths of Second (2 digits)

KYWD

Keyword (ALARM, NOTICE, COMMAND, or STATUS)

::::

System Diagnostic Information

<CR>

Carriage Return Character (ASCII 13)

<LF>

Line Feed (ASCII 10)

An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered

into the Event History Log with a cleared status.
If a port is operating in Terminal mode and is connected to a computer, you can

use key combinations at any time to print selected information:
Esc+H

Prints the entire log with a firmware version header

To use a key combination, hold down the Esc key and press the letter key.