Bypass mode, 2 bypass mode – Powerware 9330 User Manual

Page 80

Advertising
background image

6--6

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

6.2.2

Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, load

fault, or internal failure. The bypass source supplies the commercial AC power to

the load directly.
Figure 6---3 shows the path of electrical power through the UPS system when

operating in Bypass mode.

CAUTION:

The critical load is not protected while the UPS is in Bypass mode.

CB1

CB2

K1

K5

K3

K2

Open

Closed

Breakers Contactors

Main Power Flow

Energized

De--Energized

Trickle Current

RECTIFIER

BOOST

CONVERTER

INVERTER

BYPASS MODE

CHARGER

BATTERY

STATIC

SWITCH

MAINTENANCE

BYPASS SWITCH

MAINTENANCE

BYPASS SWITCH

Figure 6---3. Path of Current Through the UPS in Bypass Mode

In Bypass mode, the output of the system is provided with three phase AC power

directly from the system input. While in this mode, the output of the system is not

protected from voltage or frequency fluctuations or power outages from the source.

Some power line filtering and spike protection is provided to the load but no active

power conditioning or battery support is available to the output of the system in the

Bypass mode of operation.
The internal bypass is comprised of a solid state silicon controlled rectifier (SCR)

static switch (SSW), and a back feed protection contactor (K5). The static switch is

rated as a continuous duty device that is used anytime the boost converter and

inverter is unable to support the applied load. The static switch is wired in series

with the back feed protection contactor and together they are wired in parallel with

Advertising