Installing options cabinet internal power wiring – Powerware 9330 User Manual

Page 52

Advertising
background image

2--26

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

2.4.3

Installing Options Cabinet Internal Power Wiring

1.

Remove left front solid panel, and right front vented panel from the Powerware

9330 (10 kVA---20 kVA) UPS cabinet or left front solid panel and front vented

panels from Powerware 9330 (25 kVA---40 kVA) UPS cabinet. Front panels are

secured with magnetic latches and are removed by pulling panels straight

forward to disengage magnetic latches (see Figure 2---1).

2.

Remove screws securing UPS internal safety shield panel and remove panel to

gain access to input and output terminals.

3.

Route input and output cables from Options cabinet through wireway to UPS

terminal blocks. Refer to Appendix A of this manual for wiring access

information.

4.

If wiring a single feed system, proceed to step 5; if wiring a dual feed system,

proceed to step 7.

5.

Connect phase A, B, C, and Neutral rectifier and bypass input power wiring

from the Options cabinet to the bypass input terminals in the UPS cabinet.

Refer to Appendix A of this manual for wiring and termination requirements and

wiring access information. Note wiring connections for single feed systems.

6.

Proceed to step 10.

7.

Disconnect single feed jumpers from phase A, B, and C terminals on Input

Breaker CB1 and Input Terminal strip TB2 in UPS cabinet. Remove jumpers

from cabinet.

8.

Connect phase A, B, and C mains input power wiring from Options cabinet to

the rectifier input terminals on Input Breaker CB1 in the UPS cabinet. Refer to

Appendix A of this manual for wiring and termination requirements and wiring

access information. Note wiring connections for dual feed systems.

9.

Connect phase A, B, C, and Neutral bypass input power wiring from Options

cabinet to the bypass input terminals on Input Terminal strip TB2 in the UPS

cabinet. Refer to Appendix A of this manual for wiring and termination

requirements and wiring access information. Note wiring connections for dual

feed systems.

10.

Connect phase A, B, and C and Neutral output power wiring from the Options

cabinet to the output terminals in the UPS cabinet. Refer to Appendix A of this

manual for termination requirements and wiring access information.

11.

Secure the UPS by reinstalling safety shield panels, front vented panels, and

front solid panel.