4--2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

TB2

TB1

COVER

BOTTOM ENCLOSURE

Figure 4---2. Remote EPO Control (inside view of cover and bottom of enclosure)

3.

Mount cover to Remote EPO switch enclosure bottom, as shown in

Figure 4---2, for easier wiring.

NOTE: A separate conduit is required for each UPS connected to the Remote EPO

switch.

4.

Install wiring from the Remote EPO switch using ½-in. conduit through the

Customer Interface conduit landing plate on the rear of the UPS cabinet. Refer

to Appendix A, Drawing 164201300---8, for conduit landing area and terminal

board location, and Drawing 164201300---2 for terminal wiring assignments.

5.

Connect the Remote EPO wiring as shown in Tables 4---1 and 4---2 and Figure

4---2.

6.

If you are installing multiple Remote EPO stations, wire additional stations in

series with the first Remote EPO.