DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION: G

1 of 5

051502

CUSTOMER INTERFACE WIRING

INSTALLATION NOTES

164201300---2

A---19

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

1.

Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control

wiring in separate conduit from the power wiring. The wire should be rated at 150 volts,

5 amp minimum.

2.

Refer to Tables X, Y, and Z and to Chapters 2, 5 and 6 of this manual for customer

interface wiring.

Table X. Customer Interface Inputs and Outputs

Terminal TB2

Name

Description

1

BLDG ALARM 1

Programmable UPS alarm. Activated by a remote dry

2

BLDG ALARM 1 RTN

Programmable UPS alarm. Activated by a remote dry

contact closure.

3

BLDG ALARM 2

Programmable UPS alarm. Activated by a remote dry

4

BLDG ALARM 2 RTN

Programmable UPS alarm. Activated by a remote dry

contact closure.

5

BLDG ALARM 3

Programmable UPS alarm. Activated by a remote dry

6

BLDG ALARM 3 RTN

Programmable UPS alarm. Activated by a remote dry

contact closure.

7

BLDG ALARM 4

Programmable UPS alarm. Activated by a remote dry

8

BLDG ALARM 4 RTN

Programmable UPS alarm. Activated by a remote dry

contact closure.

Terminal TB4

1

CAN H

2

CAN L

Parallel CAN Input

3

RTN

Parallel CAN Input

Terminal TB5

1

Not Used

2

Not Used

3

EXTERNAL EPO

Dry contact used to activate remote EPO of UPS

4

EXTERNAL EPO RTN

Dry contact used to activate remote EPO of UPS.

5

Not Used

6

RTN

Terminal TB6

1

RELAY 1 RTN

2

RELAY 1 NO

General purpose NO and NC relay contacts.

3

RELAY 1 NC

General purpose NO and NC relay contacts.

Terminal TB7

1

RELAY 2 RTN

2

RELAY 2 NO

General purpose NO and NC relay contacts.

3

RELAY 2 NC

General purpose NO and NC relay contacts.

X---Slot 4

Terminal

1

UTIL_FAIL

Input used to indicate utility power failure

2

ON_BYPASS

Input used to indicate On Bypass status of UPS

3

BATTERY_LOW

Contacts used to indicate Battery Low status of UPS