Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

6.2

UPS Modes

The UPS system functions automatically to supply AC electrical power to the critical

load. There are four standard operation modes:

·

In Normal mode, the critical load is supplied by the inverter, which derives its power
from rectified utility AC power. In this mode, the battery charger also provides charging

current for the battery, if needed.

·

In Battery mode, the battery provides DC power, which maintains inverter operation.
The battery supports the critical load.

·

In Bypass and High Efficiency mode, the critical load is directly supported by utility
power.

·

In Maintenance Bypass mode, the critical load is directly supported by utility power, but
the UPS can be shut down for maintenance. This is accomplished by the operator

moving the Maintenance Bypass Switch to Bypass.

The UPS continually monitors itself and the incoming utility power, and

automatically switches between these modes as required, with no operator

intervention, except for the Maintenance Bypass mode. The sophisticated

detection and switching logic inside the UPS ensures that operating mode changes

are automatic and transparent to the critical load. The UPS switches operating

modes in response to these

system events:

·

A command is an intervention that is externally initiated by an operator or by some site
action. A command causes the UPS to switch operating modes; it usually does not

require any further action by you.

·

A notice is a minor system event that may or may not require your attention.

·

An alarm is a system event that requires immediate operator intervention.

System events, alarm horns, and indicator lights are described in Chapter 11,

“Responding to System Events.”
The following descriptions provide the differences in UPS operating modes.