10--3

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

The RMP contains a local horn and the following backlit status indicators:

NORMAL

The UPS is energized (either with utility power

or battery backup) and is supplying

conditioned power to the critical load.
BYPASS

The bypass source is supplying the critical

load. Usually this means that the UPS is not

energized. The load is not protected in Bypass

mode, and a horn sounds after 30 seconds.
ALARM

The UPS system is issuing an alarm.

Conditions that affect the current UPS mode

are indicated by the alarm lamps and horn on

the UPS.
BATTERY

The UPS battery backup is supplying the

critical load. The utility power is either

interrupted or out of specification. The

NORMAL indicator is also lit. After 30 seconds

of run time, the alarm indicator will illuminate

and a horn sound.