Powerware 9330 User Manual

Page 179

Advertising
background image

DESCRIPTION:

DATE:

DRAWING NO:

8 of 17

SHEET:

REVISION: D

NOTE:

Callout letter

and

map to drawing #164201300---6

,

, ,

053001

164201300---1

POWER WIRING INSTALLATION NOTES

D

D

A---9

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table L. Ratings & External Wiring Requirements for

Powerware 9330 (25 kVA---40 kVA)

Options Cabinet OUTPUT Transformer

Ratings 50/60 Hz

Basic unit ratings at

Voltage

Output

Conductor

g

0.7 lagging PF load

Series/

Model

kVA/KW

Input

Output

Output

Current

(Amps)

Minimum

Size

40/25

23.8/16.6

208

208

66

4

40/25

23.8/16.6

208

480

28.6

10

AC Output from

40/30

28.5/20

208

208

79

3

AC

OUTPUT

AC Output from

Output Transformer

to Critical Load

40/30

28.5/20

208

480

34.3

8

OUTPUT to Critical Load

(0.95min.PF)

40/35

33.2/23.3

208

208

92.4

2

(0.95min.PF)

3 , 1 Neutral, 1 gnd

40/35

33.2/23.3

208

480

40

8

g

40/40

38/26.6

208

208

105.5

1

40/40

38/26.6

208

480

45.7

6

Table M. Ratings & External Wiring Requirements for

Powerware 9330 (25 kVA---40 kVA)

Options Cabinet OUTPUT Without Output Transformer

Ratings 50/60 Hz

Basic unit ratings at

Voltage

Output

Conductor

g

0.7 lagging PF load

Series/

Model

kVA/KW

Input

Output

Output

Current

(Amps)

Minimum

Size

AC Output from Output

40/25

25/17.5

208

208

69.4

4

AC

OUTPUT

AC Output from Output

to Critical Load

40/30

30/21

208

208

83

2

OUTPUT to Critical Load

(0.95min.PF)

3  1 N

l 1

d

40/35

35/24.5

208

208

97

1

(

)

3 , 1 Neutral, 1 gnd

40/40

40/28

208

208

111

1/0

Advertising