14.

Install side panel removed from the UPS cabinet to the right side of the Battery

cabinet. Secure with screws removed from Battery cabinet.

15.

When all wiring is complete, proceed to Chapter 3 and connect battery strings

in accordance with instructions contained in paragraph 3.4.2.

16.

Using retained hardware, reinstall shipping brackets previously removed, to

front and rear of Battery cabinet with the angle facing outward.(see

Figures 2---6 or 2---8).

17.

Secure the front of Battery cabinet to the front of the UPS cabinet with the long

flat grounding/mounting bracket from the installation kit (see Figures 2---6 or

2---8). Use hardware provided in the kit to secure the bracket.

18.

Remove the top side panel mounting screw (tie/grounding bracket location in

Figure 2---6) from both the Battery and UPS cabinets.

19.

Secure the back of Battery cabinet to the back of the UPS cabinet with the

tie/grounding bracket. Secure the bracket with the side panel mounting

screws.

20.

Install side panel removed from the UPS cabinet to the right side of the Battery

cabinet. Secure with screws removed from Battery cabinet.

21.

Secure cabinets to floor with contractor supplied hardware.

22.

When all wiring is complete, proceed to Chapter 3 and connect battery strings

in accordance with instructions contained in paragraph 3.4.2.

2.3.3

Joining Additional Battery Cabinets

To join additional battery cabinets, perform the following steps. Refer to

Figure 2---5 for non-permanent installation or Figure 2---6 for permanent installation

of the Powerware 9330 (10 kVA---20 kVA) UPS and Figure 2---7 for non-permanent

installation or Figure 2---8 for permanent installation of the Powerware 9330

(25 kVA---40 kVA) UPS.

1.

Roll the Battery cabinet to a spot near the right side of the previously installed

Battery cabinet.

2.

Remove front vented panels from the Battery cabinets. The front panels are

secured with magnetic latches and are removed by pulling panels straight

forward to disengage magnetic latches (see Figure 2---1).

3.

Remove right side outside panel from previously installed Battery cabinet.

Retain hardware.

4.

Remove right side panel from new Battery cabinet. Retain hardware.

5.

Install side panel removed from the new Battery cabinet to the right side of the

previously installed Battery cabinet. Secure with screws removed from Battery

cabinet.

6.

Find the battery cable with 2-pole connector in the new Battery cabinet. Route

this connector into the previously installed Battery cabinet and mate with the

matching connector in the cabinet (see Figures 2---5, 2---6, 2---7, or 2---8).

7.

Push the new Battery cabinet against the right side of the previously installed

Battery cabinet.