Battery mode, 4 battery mode – Powerware 9330 User Manual

Page 83

Advertising
background image

6--9

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

6.2.4

Battery Mode

The UPS transfers to Battery mode automatically if a utility power outage occurs, or

if the utility power does not conform to specified parameters. In Battery mode, the

battery provides emergency DC power that the inverter converts to AC power.
Figure 6---5 shows the path of electrical power through the UPS system when

operating in Battery mode.

CB1

CB2

K1

K5

K3

K2

Open

Closed

Breakers Contactors

Main Power Flow

Energized

De--Energized

Trickle Current

RECTIFIER

STATIC

SWITCH

BOOST

CONVERTER

INVERTER

BATTERY MODE

CHARGER

BATTERY

MAINTENANCE

BYPASS SWITCH

MAINTENANCE

BYPASS SWITCH

Figure 6---5. Path of Current Through the UPS in Battery Mode

During a utility power failure, the rectifier no longer has an AC utility source in which

to supply the DC output current required to support the battery charger and boost

converter. The input contactor (K1) is opened, the battery charger is turned off, and

battery SCR (Q10) and battery contactor (K2) both receive signals to turn on

enable to supply battery power to the system. Because the battery SCR is an

electronic device, it supplies momentary battery power to the system during the

time it takes the contacts of K2 to close. Energy stored in the battery is supplied

instantaneously to the boost converter so that the inverter and customers load can

be supported without interruption. If the bypass is common with the rectifier input,

the Feed Back Protection contactor (K5) will also open. The opening of contactors

K1 and K5 prevent static system voltages from bleeding backwards through the

static switch and rectifier snubber components and re---entering the input source.
While in battery mode, the UPS will enunciate an audible horn, light a visual

indicator lamp on the front panel (System Normal, On Battery), and make an entry

into the alarm event history. As the battery discharges, the boost converter and

inverter constantly makes minute adjustments enable to maintain a steady output.

The UPS will remain in this operating mode until the input power to the rectifier is

again within the specified voltage or frequency acceptance windows.

Advertising