Installing the UPS System

2.1

Preliminary Installation Information

WARNING:

Installation should be performed only by qualified personnel.

Refer to the following while installing the UPS system:

·

Refer to Appendix A of this manual for installation drawings and additional

installation notes.

·

Dimensions in this manual are in millimeters and inches.

·

Do not tilt the cabinets more than

10˚ during installation.

·

The conduit landing plates are to be removed to add conduit landing holes as

required. Plate material is 16 gauge steel (0.060 in. thick).

·

The cabinets must be installed on a level floor suitable for computer or

electronic equipment.

·

If perforated floor tiles are required for ventilation, place them in front of the

UPS. Refer to Table AA in Appendix A for equipment weight and point loading.

·

Details about control wiring are provided in each procedure for connecting

options and features. Drawing 164201300---2 and Tables X and Y in Appendix A

identify the control wiring terminations.