Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Understanding UPS

Operation

6.1

Looking Inside the UPS System

The Powerware 9330 is a continuous duty, solid-state, transformerless (at 208

VAC), three phase, true online system that provide conditioned and uninterruptible

AC power to the UPS systems output. The UPS supports process control, data

processing, telecommunications/PBX, research, and non---patient medical

equipment. The Powerware 9330 maintains power to the critical loads during

commercial electrical power brownout, blackout, overvoltage, undervoltage, and

out-of-tolerance frequency conditions.
The basic system consists of a rectifier, battery charger, DC booster, inverter,

monitoring/operation control panel, integrated communications server, and

microprocessor controlled (DSP) logic.
In this manual, the power required by your equipment is called the

critical load. The

UPS supplies the critical load with conditioned power that is synchronized with your

utility power. Figure 6---1 shows the main elements of the UPS.