3 ups system output – Powerware 9330 User Manual

Page 168

Advertising
background image

15--2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

15.3

UPS System Output

DC Filtering

Ripple voltage less than 0.5% peak to peak

UPS Output Capacity

100% rated current at 0.7 power factor

Output Voltage Regulation

1% (10% to 100% load)

Output Voltage Adjustment

(Nominal +/--5%)

480 VAC nominal, adjustable from 456 VAC

to 504 VAC (50/60 Hz)

208 VAC nominal, adjustable from 198 VAC

to 218 VAC (50/60 Hz)

Output Current

Refer to Appendix A, Tables A through F, for 10,

15, and 20 kVA Models and Tables G through M,

for 25, 30, 35, and 40 kVA Models.

Output Voltage Harmonic Content

3% max THD, 2% max single (linear load)

Output Voltage Balance

3% for 100% maximum load imbalance

(linear load)

Output Voltage Phase

Displacement

3˚ for 100% maximum load imbalance (linear

load)

Output Transients

5% for 100% load step or removal

Frequency Regulation

0.01 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +10%, ---15% of

output setting; bypass within 0.5 Hz

Frequency Slew Rate

1 Hz per second maximum (adjustable)

Overload Capability

1

101---110% for 10 minutes

1

111---125% for 1 minute

Maximum Output Capability

300% peak for 10 cycles without bypass