Physical interface, Table 9, Serial communication options – Vaisala Hydromet Data Collection Platform User Manual
Page 111

Chapter 3 _____________________________________________ Configuring Modules and Sensors
VAISALA______________________________________________________________________ 109
Physical Interface
The QML logger has five different types of optional serial interfaces
available for the sensor connections.
The serial communications options are listed in
:
Table 9
Serial Communication Options
Interface
Communication
Module
Application
RS-232
Dual RS-232 module
DSU232
(two RS-232)
Distance <20 m
Single sensor
Lowest electrical interference
tolerance
Full duplex communication
RS-485
(4-wire)
Isolated RS-485
module DSI485
Distance up to 1500 m
Single sensor
Better interference tolerance
Full duplex communication
RS-485
(2-wire)
Dual RS-485
modules DSI485,
DSI486
(two RS-485)
Distance up to 1500 m
Several sensors
Better interference tolerance
Half duplex communication
Modem
Fixed line modem
module DMX501
Long distances or extreme
interference conditions
SDI
Dual RS-485 module
DSI486
SDI sensors
NOTE
The recommended connection interface is 2-wire RS-485 with a dual
RS-485 module in the QML logger. This allows an interference-
tolerant connection with the possibility to connect several sensors to
the same serial line.
NOTE
Wiring of the data and power lines depends on the application.