Chapter 3 _____________________________________________ Configuring Modules and Sensors

VAISALA_______________________________________________________________________ 57

Configuring Nokeval 7470 Data Values

Data is sent to the Nokeval converter through a report containing a valid
Nokeval command with data values. In the Reports view, create a
separate StringForm report for each command to be sent. Proceed as
follows:

1.

Set a space character as the cell separator of the report.

2.

The first cell must contain the address of the Nokeval device to
which the command is sent, followed by a valid Nokeval
command. For example, \x80OUT CH 1. See

Figure 21 on page

57

.

0711-118

Figure 21

Reports View: Setting Up Report for Nokeval

Give the address as an 8-bit hexadecimal value where the highest
bit is always set. The hexadecimal value is given in the report using
the special character code \x. For example, if the device address is
0, then the first report field should start with \x80. If the device
address is 2, then the field starts with \x82.