Transmission control for secondary transmissions, Table 20, Command. refer to – Vaisala Hydromet Data Collection Platform User Manual

Page 179: Transmission control, The starting time of the

Advertising
background image

Chapter 4 ________________________________________________ Configuring Telemetry Options

VAISALA______________________________________________________________________ 177

Transmission Control for Secondary
Transmissions

Set up the transmission control for secondary transmissions similarly to
primary transmission using the spset command. However, different
control parameters are required for secondary transmissions. The
transmission control parameters are listed in

Table 20 on page 177

.

The unitload setting (goes_sec_unitload) defines the maximum allowed
transmission time per day on the secondary channel. For example, when
unitload is set to 8, then a maximum transmission time of 8 minutes is
allowed within every 24-hour interval.

The divisor of unitload interval setting (goes_sec_load_div) divides this
interval of 24 hours into shorter periods. For example, when unitload is
set to 8, and the unitload divisor (goes_sec_load_div) is set to 4, then a
maximum transmission time of 2 minutes is allowed within every 6-
hour interval.

The total transmission time within an interval will never exceed the
defined unitload. When the unitload limit has been reached, all further
secondary transmissions within the interval will be stopped.

Table 20

Transmission Control Parameters for Secondary
Transmissions

Parameter

Value

Description

goes_sec_window

0 ... n seconds Length of the interval within which

the report is randomly transmitted
(Required)

goes_sec_repeat

0 ... 2 times

Number of randomly repeated
transmissions (Required)

goes_sec_channel

0 ... 266

Channel number of secondary
transmissions (Required)

goes_sec_unitload

1 ... n minutes Unitload limit in minutes per day

(Required)

goes_sec_load_div

1 ... n

Divisor of the unitload interval
(Optional; the default value (1) is
used if not defined)

goes_sec_bps

100, 300, or
1200

Bit rate of secondary transmissions
(Optional; if not set, the bit rate of
primary transmissions set in Lizard is
used)

Advertising