Gprs modem -dependent configurations, Application alternatives, Autosend and/or polled operation – Vaisala Hydromet Data Collection Platform User Manual

Page 150

Advertising
background image

User's Guide ______________________________________________________________________

148 _________________________________________________________________ M210933EN-C

GPRS Modem -Dependent
Configurations

In addition to data calls and SMS messages, the GPRS modem can be
used to transfer data over the Internet.

Depending on the QML logger software version, GPRS
communications can be configured in two different ways. For software
version 6.00 and above, the TCP/IP functionality is provided directly by
the QML logger. For instructions, see

GPRS-IP Modem on page 209

.

For software versions earlier than 6.00, the additional iConnector
module is required for TCP/IP connectivity. For instructions on GPRS
configuration with the iConnector module, see section

GPRS

Configuration Using the iConnector Module on page 365

.

Application Alternatives

Autosend and/or Polled Operation

The autosend and poll functions can be freely mixed. For example, a
report that is automatically sent using e-mail transmission can also be
configured to be polled with a data call and issuing appropriate poll
command.

Another example of mixed use is an application where data is
periodically retrieved using data calls or polling, but urgent alarm
messages are sent immediately using SMS transmission.

To enable polling, enter the polling string as the Poll command
parameter and select Answer incoming calls in the Options dialog.

NOTE

The poll string sent by the remote system must always be terminated
with carriage return (<CR>, ASCII character 13). You do not need to
configure it to the Poll command parameter, as it is automatically
expected.

Advertising