Vaisala Hydromet Data Collection Platform User Manual

Page 114

Advertising
background image

User's Guide ______________________________________________________________________

112 _________________________________________________________________ M210933EN-C

The following example describes how to access the PWD sensor with
device identifier 1, connected to the M60212 module in Lizard and
using a DSI486 module. Note that all open or close commands are not
echoed. In this case, input to PWD has no echo, either.

1.

Type open to open the QML logger command shell.

Service connection opened (COM0)

/ >

2.

Type open DSI486_1_1 to open a pass-through connection to the
serial line.

/ > open DSI486_1_1

Terminal I/O re-routed to DSI486_1_1

3.

Type open 1 to open the PWD command shell.

1 PWD OPENED FOR OPERATOR COMMANDS

>

You can now use the commands described in the PWD sensor user
manual to perform configuration and maintenance operations.

4.

To close the connection, type close.

Terminal I/O restored to ADCL shell
Service connection closed

NOTE

Use the SYSINFO PORTS command to find out which connectors to
use.

NOTE

Some sensors require that you first close their service connection.
Include the device identifier, for example, close 1.

Close the sensor service connection first, and then close the QML
logger connection using the close command alone.