Configuring communication port of nokeval 7470, Figure 18 – Vaisala Hydromet Data Collection Platform User Manual

Page 56

Advertising
background image

User's Guide ______________________________________________________________________

54 __________________________________________________________________ M210933EN-C

Configuring Communication Port of Nokeval 7470

One or several Nokeval devices are connected to the QML logger
through an RS-485 communication port. The device can be connected
to the following RS-485 ports:

-

Integrated RS-485 port (COM1)

-

Isolated RS-485 port (2-wire or 4-wire connection)

In the Optional hardware view of Lizard Setup Software, configure
the selected RS-485 port as follows:

1.

In the Line parameters frame, leave the default values (9600, 8, 1,
none), unless the Nokeval device is to be otherwise configured. See

Figure 18 on page 54

.

2.

In the Wiring options frame, select the Two wire connection type
from the list (isolated DSI485A only).

3.

Leave all options unselected in the Handshake options frame.

0711-115

Figure 18

Optional Hardware View: Configuring
Communication Port for Nokeval 7470 (1/2)