Ceilometers – Vaisala Hydromet Data Collection Platform User Manual

Page 122

Advertising
background image

User's Guide ______________________________________________________________________

120 _________________________________________________________________ M210933EN-C

Ceilometers

Ceilometers produce almost equal data using the same data messages.

The default communication parameters for service and data port are as
follows:

The sensor commands for interface configuration are as follows:

Message availability by sensor type is as follows:

Parameter

Value

Speed

2400 bps

Parity

even

Data

7

Stop

1

Handshake

none

Operation

Command(s)

Description

Set polled

SET MESSAGE TYPE
<type>

SET MESSAGE MODE
POLLING

Sets message type, where
<type> is MSG1, MSG6 or
MSG 61. Disables automatic
transmission.

Set auto tx

SET MESSAGE TYPE
<type>

SET MESSAGE MODE
AUTOSEND

Sets message type, where
<type> is MSG1, MSG6 or
MSG 61. Enables automatic
transmission.

Set ID

SET UNIT_ID <ID>

Sets unit ID, where <ID> is a
single character 1...Z.

Set interface
type

SET PORT DATA
INTERFACE
<type>

Sets interface type for the
data connection. <type> is
RS-232 or RS-485_2W.

Sensor

Messages

CT25

1,6

CT25KAM

1,61

CL31

CT25 message 1,6

NOTE

In order to have messages 6 or 61 available, you need to purchase the
sky condition option separately.