3 minimizing noise pickup from external cabling – INFICON XTC/3 Thin Film Deposition Controller Operating Manual User Manual

Page 40

Advertising
background image

2 - 6

PN

07

4-

44

6-

P1

J

XTC/3 Operating Manual

In many cases, a braided ground strap is sufficient. However, there are cases when
a solid copper strap (0.030 in. thick x 1 in. wide) is required because of its
lower RF impedance.

Figure 2-3 System grounding diagram

2.2.3 Minimizing Noise Pickup From External Cabling

When a XTC/3 is fully integrated into a deposition system, there are many wire
connections, each a potential path for noise to reach the inside of XTC/3. The
likelihood of these wires causing a problem can be greatly diminished by adhering
to the following guidelines.

Use shielded coax cable or twisted pairs for all connections.

Minimize cable lengths.

Avoid routing cables near areas that have the potential to generate high levels
of interference. For example, large power supplies such as those used for
electron beam guns or sputtering sources can be a source of large, rapidly
changing electromagnetic fields. Placing cables as little as one foot away from
these problem areas can significantly reduce noise pickup.

Be sure that a good ground system and straps are in place per the
recommendations in

section 2.2.2 on page 2-5

.

Make sure all XTC/3 covers and option panels are in place and tightly secured
with the provided fasteners.

NOTE: Always use shielded cables when making connections to the XTC/3 rear

panel to minimize electrical noise pickup.

Back Panel

Ground

Earth

Ground

Transducer

Feedthrough

Vacuum System

Stud

Advertising