Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

107

HIM Overview

Appendix B

Linking Parameters

Most parameter values are entered directly by the user. However, certain
parameters can be “linked,” so the value of one parameter becomes the value of
another. For Example: the value of an analog input can be linked to [Accel Time
2]. Rather than entering an acceleration time directly (via HIM), the link allows
the value to change by varying the analog signal. This can provide additional
flexibility for advanced applications.

Each link has 2 components:

Source parameter – sender of information.
Destination parameter – receiver of information.

Most parameters can be a source of data for a link, except parameter values that
contain an integer representing an ENUM (text choice). These are not allowed,
since the integer is not actual data (it represents a value).

Table 15

lists the

parameters that can be destinations. All links must be established between equal
data types (parameter value formatted in floating point can only source data to a
destination parameter value that is also floating point). A maximum of ten links is
allowed.

Establishing A Link

Step

Example Displays

1. Select a valid destination parameter (see

Table 15

) to be linked

(refer to

page 106

). The parameter value screen will appear.

2. Press the

(Enter) key to edit the parameter. The cursor will

move to the value line.

3. Press the

key and then the

key. Next, press the

or

key to change “Present Value” to “Define Link.” Then press the
(Enter) key.

4. Enter the Source Parameter Number and press the

(Enter) key.

The linked parameter can now be viewed two different ways by
repeating steps 1-4 and selecting “Present Value” or “Define Link.” If
an attempt is made to edit the value of a linked parameter,
“Parameter is Linked!” will be displayed, indicating that the value is
coming from a source parameter and cannot be edited.

5. To remove a link, repeat steps 1-5 and change the source parameter

number to zero (0).

6. Press the

key to return to the group list.

ALT

Sel

Esc

Min: 0.1 Secs
Max: 3600.0 Secs

Dflt: 10.0 Secs

Present Value

FG

P

: Parameter

Accel Time 1

Accel Time 2

Decel Time 1

Parameter:

#141

Accel Time 2

Link:

017

Analog In1 Value

Define Link