Testpoint Codes and
Functions

Select testpoint with [Testpoint x Sel], parameters 234/236. Values can be
viewed with [Testpoint x Data], parameters 235/237.

No.

(1)

(1) Enter in [Testpoint x Sel].

Description

Units

Values

Minimum

Maximum

Default

01

DPI Error Status

1

0

255

0

02

Heatsink Temp

0.1 degC

–100.0

100.0

0

03

Active Cur Limit

1

0

32767

0

04

Active PWM Freq

1 Hz

2

10

4

05

Life MegaWatt Hr

(2)

(2) Use the equation below to calculate total Lifetime MegaWatt Hours.

0.0001 MWh

0

214748.3647

0

06

Life Run Time

0.0001 Hrs

0

214748.3647

0

07

Life Pwr Up Time

0.0001 Hrs

0

214748.3647

0

08

Life Pwr Cycles

1

0

4294967295

0

09

Life MW-HR Fract

(2)

1

0

4294967295

0

10

MW-HR Frac Unit

(2)

1

0

4294967295

0

11

MCB Life Time

0.0001 Hrs

0

214748.3647

0

12

Raw Analog In 1

1

0

0

13

Raw Analog In 2

1

0

0

16

CS Msg Rx Cnt

1

0

65535

0

17

CS Msg Tx Cnt

1

0

65535

0

18

CS Timeout Cnt

1

0

255

0

19

CS Msg Bad Cnt

1

0

255

0

22

PC Msg Rx Cnt

1

0

65535

0

23

PC Msg Tx Cnt

1

0

65535

0

24-29

PC1-6 Timeout Cnt

1

0

255

0

30

CAN BusOff Cnt

1

0

65535

0

31

No. of Analog Inputs

1

0

x

0

32

Unfiltered Bus Voltage

1

0

65535

0

33

MTO Norm Mtr Amp

0.1 Amps

0

65535

0

36

DTO-Cmd DC Hold

1

0

32767

0

37

Control Bd Temp

0.1

0.0

60.0

0.0

38

Junction Temp

0.1 degC

–100.0

200.0

0

39

Gnd Warn Level

0.1 Amps

0

3276.7

0

40

In Phase Loss Level

1

0

32767

0

629

Motor OL Count

Value of Code 9

Value of Code 10

-----------------------------------------

0.1

×

Value of Code 5

+

Total Lifetime MegaWatt H

=