Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

21

Programming and Parameters

Chapter 1

Monitor File

Fi

le

Grou

p

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Re

la

te

d

MON

IT

O

R

Meter

in

g

001 [Output Freq]

Output frequency present at T1, T2 & T3 (U, V &
W)

Default:

Min/Max:
Units:

Read Only

–/+[Maximum Freq]
0.1 Hz

002 [Commanded Speed]

Value of the active Speed/Frequency Reference.
Displayed in Hz or RPM, depending on value of
[Speed Units].

Default:

Min/Max:
Units:

Read Only

–/+[Maximum Speed]
0.1 Hz
0.1 RPM

079

003 [Output Current]

The total output current present at T1, T2 & T3 (U,
V & W).

Default:

Min/Max:
Units:

Read Only

0.0/Drive Rated Amps x 2
0.1 Amps

004 [Torque Current]

Based on the motor, the amount of current that is
in phase with the fundamental voltage
component.

Default:

Min/Max:
Units:

Read Only

Drive Rating x –2/+2
0.1 Amps

005 [Flux Current]

Amount of current that is out of phase with the
fundamental voltage component.

Default:

Min/Max:
Units:

Read Only

Drive Rating x –2/+2
0.1 Amps

006 [Output Voltage]

Output voltage present at terminals T1, T2 & T3
(U, V & W).

Default:

Min/Max:
Units:

Read Only

0.0/Drive Rated Volts
0.1 VAC

007 [Output Power]

Output power present at T1, T2 & T3
(U, V & W).
[Output Power] = SQRT (3) x [Output Voltage] x
[Output Current] x [Output Powr Fctr]

Default:

Min/Max:
Units:

Read Only

0.0/Drive Rated kW x 2
0.1 kW

008 [Output Powr Fctr]

Output Power Factor =
ABS (SIN (Commanded Voltage Vector Angle -
Measured Current Vector Angle))

Default:

Min/Max:
Units:

Read Only

0.00/1.00
0.01

009 [Elapsed MWh]

Accumulated output energy of the drive.

Default:

Min/Max:
Units:

Read Only

0.0/214748352.0 MWh
0.1 MWh

010 [Elapsed Run Time]

Accumulated time drive is outputting power.

Default:

Min/Max:
Units:

Read Only

0.0/214748352.0 Hrs
0.1 Hrs

011 [MOP Reference]

Value of the signal at MOP (Motor Operated
Potentiometer).

Default:

Min/Max:
Units:

Read Only

–/+[Maximum Speed]
0.1 Hz
0.1 RPM

079

012 [DC Bus Voltage]

Present DC bus voltage level.

Default:

Min/Max:
Units:

Read Only

0.0/Based on Drive Rating
0.1 VDC

013 [DC Bus Memory]

6 minute average of DC bus voltage level.

Default:

Min/Max:
Units:

Read Only

0.0/Based on Drive Rating
0.1 VDC

014 [Elapsed kWh]

Accumulated output energy of the drive.

Default:

Min/Max:
Units:

Read Only

0.0/429496729.5 kWh
0.1 kWh

016
017

[Analog In1 Value]
[Analog In2 Value]

Value of the signal at the analog inputs.

Default:

Min/Max:

Units:

Read Only

0.000/20.000 mA
–/+10.000V
0.001 mA
0.001 Volt