Start at powerup, Stop mode, Start at powerup stop mode – Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 140

Advertising
background image

140

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Appendix C

Application Notes

Start At PowerUp

A powerup delay time of up to 30 seconds can be programmed through [Powerup
Delay], parameter 167. After the time expires, the drive will start if all of the start
permissive conditions are met. Before that time, restart is not possible.

Stop Mode

The PowerFlex 700 offers several methods for stopping a load. The method/
mode is defined by [Stop/Brk Mode A/B], parameters 155 and 156. These
modes include:

Coast
Ramp
Ramp to Hold
DC Brake
Fast Brake

Additionally, [Flux Braking], parameter 166 can be selected separately to provide
additional braking during a “Stop” command or when reducing the speed
command. For “Stop” commands, this will provide additional braking power
during “Ramp” or “Ramp to Hold” selections only. If “Fast Brake” or “DC Brake”
is used, “Flux Braking” will only be active during speed changes (if enabled).

A “Ramp” selection will always provide the fastest stopping time if a method to
dissipate the required energy from the DC bus is provided (that is, resistor brake,
regenerative brake, etc.). The alternative braking methods to external brake
requirements can be enabled if the stopping time is not as restrictive. Each of
these methods will dissipate energy in the motor (use care to avoid motor
overheating).

Table 16

describes several braking capability examples.

[Powerup Delay]

Time Expired?

Start At PowerUp

Yes

Powerup Terminated!

Normal Mode

No

No

No

Powerup Start

Is the terminal block Run,

Run Forward or Run Reverse

Input Closed?

Yes

Yes

All Start Permissives Met?

1. No fault conditions present.

2. No Type 2 alarm conditions present.

3. The terminal block programmed

enable input is closed.

4. The Stop input (from all sources) is

received.

Advertising