Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

91

Troubleshooting

Chapter 2

Alarm Descriptions

Table 4 - Alarm Descriptions and Actions

Alarm

No

.

Ty

pe

(1)

Description

AdjVoltRef Cflct

33

1 Invalid adjustable voltage reference selection conflict.

Analog In Loss

5

1 An analog input is configured for “Alarm” on signal loss and signal loss has occurred.

Bipolar Conflict

20

2 Parameter 190 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more of the

following digital input functions is configured: “Fwd/Reverse,”
“Run Forward,” “Run Reverse,” “Jog Forward” or “Jog Reverse.”

Brake Slipped

32

2 Encoder movement has exceeded the level in [BrkSlipCount] after the brake was set.

Brake Slipping

16

2 Brake slip procedure is in progress.

Decel Inhibt

10

1 Drive is being inhibited from decelerating.

Dig In ConflictA

17

2 Digital input functions are in conflict. Combinations marked with a “ ” will cause an

alarm.

Dig In ConflictB

18

2 A digital Start input has been configured without a Stop input or other functions are in

conflict. Combinations that conflict are marked with a “ ” and will cause an alarm.

Dig In ConflictC

19

2 More than one physical input has been configured to the same input function. Multiple

configurations are not allowed for the following input functions.
Forward/Reverse

Run Reverse

Bus Regulation Mode B

Speed Select 1

Jog Forward

Acc2 / Dec2

Speed Select 2

Jog Reverse

Accel 2

Speed Select 3

Run

Decel 2

Run Forward

Stop Mode B

DPI Port1 Loss

38

1 The HIM connected to DPI Port 1-3 stopped communicating to the drive. Check the HIM

connection.

DPI Port2 Loss

39

1

DPI Port3 Loss

40

1

Drive OL Level 1

8

1 The calculated IGBT temperature requires a reduction in PWM frequency. If [Drive OL Mode]

is disabled and the load is not reduced, an overload fault will eventually occur.

Drive OL Level 2

9

1 The calculated IGBT temperature requires a reduction in Current Limit. If [Drive OL Mode] is

disabled and the load is not reduced, an overload fault will eventually occur.

FluxAmpsRef
Rang

26

2 The calculated or measured Flux Amps value is not within the expected range. Verify motor

data and rerun motor tests.

Ground Warn

15

1 Ground current has exceeded the level set in [Gnd Warn Level].

v6

Acc2/Dec2

Accel 2 Decel 2 Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev

Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev

Start

Stop-

CF

Run Run Fwd Run Rev

Jog

1/2

Jog Fwd Jog Rev

Fwd/

Rev

Start
Stop-CF
Run
Run Fwd
Run Rev
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev