Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 30

Advertising
background image

30

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

084
085
086

[Skip Frequency 1]
[Skip Frequency 2]
[Skip Frequency 3]

Sets a frequency at which the drive will not
operate.

Default:
Default:
Default:

Min/Max:
Units:

0.0 Hz
0.0 Hz
0.0 Hz

–/+[Maximum Speed]
0.1 Hz

087

087 [Skip Freq Band]

Determines the bandwidth around a skip
frequency. [Skip Freq Band] is split, applying 1/2
above and 1/2 below the actual skip frequency.
The same bandwidth applies to all skip
frequencies.

Default:

Min/Max:
Units:

0.0 Hz

0.0/30.0 Hz
0.1 Hz

084
085
086

SPEED C

O

MMAND

Spd Mode

&

Limits

088 [Speed/Torque Mod]

Selects the torque reference source.

“Zero Torque” (0) - torque command = 0.

“Speed Reg” (1) - drive operates as a speed
regulator.

“Torque Reg” (2) - an external torque reference is
used for the torque command.

Default:

Options:

1

0
1
2
3
4
5
6
7

“Speed Reg”

“Zero Torque”
“Speed Reg”
“Torque Reg”
“Min Torq/Spd”
“Max Torq/Spd”
“Sum Torq/Spd”
“Absolute Min”
“Pos/Spd Prof”

053

“Min Torq/Spd” (3) - selects the smallest algebraic value to regulate to when the torque reference
and torque generated from the speed regulator are compared.

“Max Torq/Spd” (4) - selects the largest algebraic value when the torque reference and the
torque generated from the speed regulator are compared.

“Sum Torq/Spd” (5) - selects the sum of the torque reference and the torque generated from the
speed regulator.

“Absolute Min” (6) - selects the smallest absolute algebraic value to regulate to when the torque
reference and torque generated from the speed regulator are compared.

“Pos/Spd Prof” (7) - drive operates as a speed or position regulator as determined by the Profile
Step parameters (720-877) and Setup parameters (705-719).

454 [Rev Speed Limit]

Sets a limit on speed in the negative direction,
when in FVC Vector mode. Used in bipolar mode
only. A value of zero disables this parameter and
uses [Maximum Speed] for reverse speed limit.

Default:

Min/Max:

Units:

0.0 RPM

–[Max Speed]/0.0 Hz
–[Max Speed]/0.0 RPM
0.0 Hz
0.0 RPM

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

FV

ATTENTION: The speed of the drive could reach [Maximum Speed] +
[Overspeed Limit] to meet required torque when any of the torque
modes have been selected. Equipment damage and/or personal injury
can result.

FV