Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 40

Advertising
background image

40

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

DYNAMIC C

ONTROL

Stop/B

rak

e Mo

des

161
162

[Bus Reg Mode A]
[Bus Reg Mode B]

Sets the method and sequence of the DC bus
regulator voltage. Choices are dynamic brake,
frequency adjust or both. Sequence is
determined by programming or digital input to
the terminal block.
Dynamic Brake Setup
If a dynamic brake resistor is connected to the
drive, both of these parameters must be set to
either option 2, 3 or 4.
Refer to the Attention statement on page

12

for

important information on bus regulation.

Default:

Options:

1
4

0
1
2
3
4

“Adjust Freq”
“Both-Frq 1st”

“Disabled”
“Adjust Freq”
“Dynamic Brak”
“Both-DB 1st”
“Both-Frq 1st”

160
163

163 [DB Resistor Type]

Selects whether the internal or an external DB
resistor will be used.
Important: In Frame 0…2 drives, only one DB
resistor can be connected to the drive.
Connecting both an internal & external resistor
could cause damage.
If a dynamic brake resistor is connected to the
drive, [Bus Reg Mode A & B] must be set to either
option 2, 3 or 4.

Default:

Options:

2

0
1
2

“None”

“Internal Res”
“External Res”
“None”

161
162

164 [Bus Reg Kp]

Proportional gain for the bus regulator. Used to
adjust regulator response.

Default:

Min/Max:
Units:

1500

0/10000
1

165 [Bus Reg Kd]

Derivative gain for the bus regulator. Used to
control regulator overshoot.

Default:

Min/Max:
Units:

1000

0/10000
1

166 [Flux Braking]

Set to use an increase in the motor flux current to
increase the motor losses, and allow a faster
deceleration time when a chopper brake or
regenerative capability is not available. Can be
used as a stopping or fast deceleration method.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

452 [Stop Dwell Time]

Sets an adjustable delay time between detecting
zero speed and disabling the speed and torque
regulators, when responding to a stop command.
For more information, please see

Stop Dwell

Time on page 145

.

Important: Consult industry and local codes
when setting the value of this parameter.

Default:

Min/Max:
Units:

0.00 Secs

0.00/60.00 Secs
0.01 Secs

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

ATTENTION: The drive does not offer protection for externally
mounted brake resistors. A risk of fire exists if external braking resistors
are not protected. External resistor packages must be self-protected
from over temperature or the protective circuit shown in

Figure 5 on

page 111

(or equivalent) must be supplied.

ATTENTION: Equipment damage can result if a drive mounted
(internal) resistor is installed and this parameter is set to “External Res”
or “None.” Thermal protection for the internal resistor will be disabled,
resulting in possible device damage. Also see ATTENTION statement in
parameter 161/162.