Motor cntl sel – Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 24

Advertising
background image

24

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

M

O

TO

R C

O

N

TROL

To

rq A

ttribut

es

053 [Motor Cntl Sel]

Sets the method of motor control used in the
drive.
When “Adj Voltage” is selected, voltage control is
independent from frequency control. The voltage
and frequency components have independent
references and accel/decel rates. Typical
applications include non-motor loads or power
supplies.
Important: “FVC Vector” mode requires
autotuning of the motor. Being coupled to the
load will determine inertia (preferably lightly-
loaded). Total Inertia (parameter 450) will have
to be estimated if uncoupled for tuning of the
speed loop or separately adjust Ki and Kp
(parameters 445 & 446).

Default:

Options:

0

0
1
2
3
4
5

“Sensrls Vect”

“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”
“FVC Vector”
“Adj Voltage”

054 [Maximum Voltage]

Sets the highest voltage the drive will output.
Based on [Voltage Class], parameter 202.

Default:

Min/Max:
Units:

Drive Rated Volts

Rated Volts x 0.25/Rated Volts
0.1 VAC

202

055 [Maximum Freq]

Sets the highest frequency the drive will output.
Based on [Voltage Class], parameter 202. Also
refer to [Overspeed Limit], parameter 083.

Default:

Min/Max:
Units:

110.0 or 130.0 Hz

5.0/420.0 Hz
0.1 Hz

083
202

056 [Compensation]

Enables/disables correction options.

Option Descriptions
Reflect Wave

Disables reflected wave overvoltage protection for long cable lengths.
(typically enabled).

Enable Jerk

In non-FVC Vector modes, disabling jerk removes a short S-curve at the start of
the accel/decel ramp.

Ixo AutoCalc

Not functional – reserved for future enhancements.

Xsistor Diag

“0” disables power transistor power diagnostic tests which run at each start
command. “1” enables transistor diagnostic tests.

Rs Adapt

FVC w/Encoder Only - Disabling can improve torque regulation at lower speeds
(typically not needed).

Mtr Lead Rev

Reverses the phase rotation of the applied voltage, effectively reversing the
motor leads. Note: This bit is reset to “0” when parameters are reset to
factory defaults.

PWM Freq Lock

Keeps the PWM frequency from decreasing to 2 kHz at low operating
frequencies in FVC Vector mode without encoder.

DigIn DatLog

Enable [DigIn DataLogic], parameter 411.

NoSyncPWM

Disables synchronous PWM.

EncFiltStop

In FVC Vector mode only, sets the encoder filter based on parameter 416 -
[Fdbk Filter Sel] to detect when the drive is at zero speed during the stop
sequence.

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

1

0

1

1

1

0

x

0

0

x

0

0

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Enabled

0 = Disabled
x = Reserved

Bit #

Factory Default Bit Values

(1)

For current limit (except FVC Vector mode).

(2)

Firmware 6.002 and later.

(3)

Firmware 9.001 and later.

Reflec

t W

av

e

Enable Jerk

(1)

Ixo A

ut

oC

alc

Xsist

or D

iag

Rs A

dapt

Mtr L

ead Rev

PWM F

reqL

ock

TPEnc

dless

EncF

iltSt

op

(3)

Digin Da

tL

og

(2)

NoS

yncPWM

(2)