Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

43

Programming and Parameters

Chapter 1

DY

NAMIC C

O

NTROL

Rest

ar

t M

odes

182 [Sleep Level]

Defines the analog input level that will stop the
drive.

Default:

Min/Max:

Units:

5.000 mA, 5.000 Volts

4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
0.001 mA
0.001 Volts

183

183 [Sleep Time]

Defines the amount of time at or below [Sleep
Level] before a Stop is issued.

Default:

Min/Max:
Units:

0.0 Secs

0.0/1000.0 Secs
0.1 Secs

182

Po

w

er

L

os

s

177 [Gnd Warn Level]

Sets the level at which a ground warning fault
will occur. Configure with [Alarm Config 1].

Default:

Min/Max:
Units:

3.0 Amps

1.0/5.0 Amps
0.1 Amps

259

184 [Power Loss Mode]

Sets the reaction to a loss of input power. Power
loss is recognized when:
DC bus voltage is

≤ 73% of [DC Bus Memory]

and [Power Loss Mode] is set to “Coast”.

DC bus voltage is

≤ 82% of [DC Bus Memory]

and [Power Loss Mode] is set to “Decel”.

Default:

Options:

0

0
1
2
3
4
5

“Coast”

“Coast”
“Decel”
“Continue”
“Coast Input”
“Decel Input”
“Decel 2 Stop”

013
185

185 [Power Loss Time]

Sets the time that the drive will remain in power
loss mode before a fault is issued.

Default:

Min/Max:
Units:

0.5 Secs

0.0/60.0 Secs
0.1 Secs

184

186 [Power Loss Level]

Sets the level at which the [Power Loss Mode]
selection will occur.

Default:

Min/Max:
Units:

Drive Rated Volts

0.0/999.9 VDC
0.1 VDC

The drive can use the percentages referenced in [Power Loss Mode] or a trigger point can be set
for line loss detection as follows:
V

trigger

= [DC Bus Memory] – [Power Loss Level]

A digital input (programmed to “29, Pwr Loss Lvl”) is used to toggle between fixed percentages
and the detection level.

187 [Load Loss Level]

Sets the percentage of motor nameplate torque
(absolute value) at which a load loss alarm will
occur.

Default:

Min/Max:
Units:

200.0%

0.0/800.0%
0.1%

211
259

188 [Load Loss Time]

Sets the time that current is below the level set in
[Load Loss Level] before a fault occurs.

Default:

Min/Max:
Units:

0.0 Secs

0.0/300.0 Secs
0.1 Secs

187

189 [Shear Pin Time]

Sets the time that the drive is at or above current
limit before a fault occurs. Zero disables this
feature.

Default:

Min/Max:
Units:

0.0 Secs

0.0/30.0 Secs
0.1 Secs

238

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

v6

ATTENTION: Drive damage can occur if proper input impedance is not
provided as explained below.
If the value for [Power Loss Level] is greater than 18% of [DC Bus Memory],
the user must provide a minimum line impedance to limit inrush current
when the power line recovers. The input impedance should be equal to or
greater than the equivalent of a 5% transformer with a VA rating 5 times
the drives input VA rating.