Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 46

Advertising
background image

46

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

UTILIT

Y

Dr

iv

e M

em

or

y

201 [Language]

Selects the display language when using an LCD
HIM. This parameter is not functional with an
LED HIM.
Options 6, 8 and 9 are “Reserved.”
This parameter is not reset when “Reset to
Defaults” is selected.

Default:

Options:

0

0
1
2
3
4
5
7
10

“Not Selected”

“Not Selected”
“English”
“Francais”
“Español”
“Italiano”
“Deutsch”
“Português”
“Nederlands”

202 [Voltage Class]

Configures the drive current rating and associates
it with the selected voltage (i.e. 400 or 480V).
Normally used when downloading parameter
sets. Min/Max & Default values will be changed
for parameters; 41-47, 54, 55, 62, 63, 69, 70-72,
82, 148, 158.
This parameter is not reset when “Reset to
Defaults” is selected.
Important: Frames 5…10 - If changing voltage
class, verify correct voltage on the fan
transformer. See “Selecting /Verifying Fan
Voltage” in the Installation Instructions,
publication

20B-IN0019

.

Default:

Options:

2
3
4
5

Based on Drive Cat. No.

“Low Voltage”
“High Voltage”
“Reserved”
“Reserved”

041

047
054
055
062
063
069

072
082
148
158

203 [Drive Checksum]

Provides a checksum value that indicates
whether or not a change in drive programming
has occurred.

Default:

Min/Max:
Units:

Read Only

0/65535
1

204 [Dyn UsrSet Cnfg]

Enables/Disables dynamic selection of user parameter sets.
Important: In dynamic mode, changes to the parameters are not saved to nonvolatile storage.
Switching user sets restores the values last saved before enabling dynamic mode.

205 [Dyn UsrSet Sel]

Selects user set if [Dyn UsrSet Cnfg] = xxxx xx11.
Important: All digital input selections (parameters 361-366) must be identical in all three user
sets for proper Dynamic User Set operation (even if only two sets are used).

206 [Dyn UserSet Actv]

Indicates the active user set and if the operation is dynamic or
normal.

Read Only

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

Bit #

Factory Default Bit Values

Dynamic Mode

Ctrl S

our

ce

Dynamic Mode

1 = Enabled

0 = Disabled

Ctrl Source

1 = [Dyn UserSet Sel]

0 = Digital Inputs

x = Reserved

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Enabled
0 = Disabled
x = Reserved

Bit #

Factory Default Bit Values

UserS

et S

el1

UserS

et S

el2

0
1
0
1

User Set 1
User Set 2
User Set 3
User Set 3

0
0
1
1

0

0

0

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Condition True

0 = Condition False
x = Reserved

Bit #

Dynamic Mode

User S

et 1

User S

et 2

User S

et 3