Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

89

Troubleshooting

Chapter 2

Pwr Brd Chksum2

105

2 The checksum read from the board does

not match the checksum calculated.

1. Cycle power to the drive.
2. If problem persists, replace drive.

Replaced MCB-PB

107

2 Main Control Board was replaced and

parameters were not programmed.

1. Restore defaults.
2. Reprogram parameters.

See Manual

28

Encoderless TorqProve has been
enabled but user has not read and
understood application concerns of
encoderless operation.

Read the “Attention” on

page 112

relating

to the use of TorqProve with no encoder.

Shear Pin

63

3 Programmed [Current Lmt Val] has

been exceeded. Enable/Disable with
[Fault Config 1] on

page 52

.

Check load requirements and [Current Lmt
Val] setting.

Software Fault

88

Microprocessor handshake error.

Replace Main Control Board.

Software Fault

89

Microprocessor handshake error.

Replace Main Control Board.

SW OverCurrent

36

1 Drive output current has exceeded the

1ms current rating. This rating is
greater than the 3 second current rating
and less than the hardware overcurrent
fault level. It is typically 200- 250% of
the drive continuous rating.

Check for excess load, improper DC boost
setting. DC brake volts set too high.

TorqPrv Spd Band

20

Difference between [Commanded
Speed] and [Encoder Speed] has
exceeded the level set in [Spd Dev
Band] for a time period greater than
[Spd Band Integrat].

1. Check wiring between drive and motor.
2. Check release of mechanical brake.

Trnsistr OvrTemp

9

1 Output transistors have exceeded their

maximum operating temperature.

1. Verify that maximum ambient

temperature has not been exceeded.

2. Check fan.
3. Check for excess load.

UnderVoltage

4

1
3

DC bus voltage fell below the minimum
value of 407V DC at 400/480V input or
204V DC at 200/240V input. Enable/
Disable with [Fault Config 1] (

page 52

).

Monitor the incoming AC line for low
voltage or power interruption.

UserSet1 Chksum

101

2 The checksum read from the user set

does not match the checksum
calculated.

Re-save user set.

UserSet2 Chksum

102

2

UserSet3 Chksum

103

2

(1) See

page 83

for a description of fault types.

Fault

No

.

Ty

pe

(1)

Description

Action