Common symptoms/ corrective actions, Common symptoms/corrective actions – Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 94

Advertising
background image

94

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 2

Troubleshooting

Common Symptoms/
Corrective Actions

Table 6 - Drive does not Start from Start or Run Inputs wired to the terminal block.

Table 7 - Drive does not Start from HIM.

Table 8 - Drive does not respond to changes in speed command.

Cause(s)

Indication

Corrective Action

Drive is Faulted

Flashing red status
light

Clear fault.
Press Stop
Cycle power
Set [Fault Clear] to 1 (see

page 52

)

“Clear Faults” on the HIM Diagnostic menu

Incorrect input wiring. Refer to the
Installation Instructions for wiring
examples.
2 wire control requires Run, Run

Forward, Run Reverse or Jog
input.

3 wire control requires Start and

Stop inputs.

Jumper from terminal 25 to 26 is

required.

None

Wire inputs correctly and/or install jumper.

Incorrect digital input
programming.
Mutually exclusive choices have

been made (i.e., Jog and Jog
Forward).

2 wire and 3 wire programming

can be conflicting.

Exclusive functions (i.e,

direction control) can have
multiple inputs configured.

Stop is factory default and is not

wired.

None

Program [Digital Inx Sel] for correct inputs (

page 63

).

Start or Run programming can be missing.

Flashing yellow status
light and “DigIn
CflctB” indication on
LCD HIM.
[Drive Status 2] shows
type 2 alarm(s).

Program [Digital Inx Sel] to resolve conflicts (

page 63

).

Remove multiple selections for the same function.
Install stop button to apply a signal at stop terminal.

Cause(s)

Indication

Corrective Action

Drive is programmed for 2 wire
control. HIM Start button is
disabled for 2 wire control unless
param. 192, bit 1 = “1.”

None

If 2 wire control is required, no action needed. See
[Save HIM Ref] on

page 44

.

If 3 wire control is required, program [Digital Inx Sel]
for correct inputs (see

page 63

).

Cause(s)

Indication

Corrective Action

No value is coming from the source
of the command.

LCD HIM Status Line
indicates “At Speed”
and output is 0 Hz.

1. If the source is an analog input, check wiring and

use a meter to check for presence of signal.

2. Check [Commanded Speed] for correct source (see

page 21

).

Incorrect reference source has been
programmed.

None

3. Check [Speed Ref Source] for the source of the

speed reference (see

page 48

).

4. Reprogram [Speed Ref A Sel] for correct source (see

page 31

).

Incorrect Reference source is being
selected via remote device or digital
inputs.

None

5. Check [Drive Status 1],

page 47

, bits 12 and 13 for

unexpected source selections.

6. Check [Dig In Status],

page 49

to see if inputs are

selecting an alternate source.

7. Reprogram digital inputs to correct “Speed Sel x”

option (see

page 63

).

Advertising