Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 93

Advertising
background image

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

93

Troubleshooting

Chapter 2

Table 5 - Alarm Cross Reference

Start At PowerUp 4

1 [Start At PowerUp] is enabled. Drive can start at any time within 10 seconds of drive

powerup.

TB Man Ref Cflct 30

2 Occurs when:

“Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363 and
[TB Man Ref Sel], parameter 96 has been reprogrammed.
No other use for the selected analog input can be programmed.
Example: If [TB Man Ref Sel] is reprogrammed to “Analog In 2,” all of the factory default
uses for “Analog In 2” must be reprogramed (such as parameters 90, 117, 128 and 179).
To correct:
Verify/reprogram the parameters that reference an analog input or
Reprogram [Digital In3] to another function or “Unused.”

TorqProve Cflct

49

2 When [TorqProve Cnfg] is enabled, [Motor Cntl Sel], [Feedback Select] and [Motor Fdbk

Type] must be properly set (see

page 115

).

UnderVoltage

2

1 The bus voltage has dropped below a predetermined value.

VHz Neg Slope

24

2 [Torq Perf Mode] = “Custom V/Hz” & the V/Hz slope is negative.

Waking

11

1 The Wake timer is counting toward a value that will start the drive.

(1) See

page 83

for a description of alarm types.

No.

(1)

(1) Alarm numbers not listed are reserved for future use.

Alarm

No.

(1)

Alarm

No.

(1)

Alarm

1

Precharge Active

15

Ground Warn

28

Ixo Vlt Rang

2

UnderVoltage

16

(2)

(2) Firmware 6.002 and later only.

Brake Slipping

29

Sleep Config

3

Power Loss

17

Dig In ConflictA

30

TB Man Ref Cflct

4

Start At PowerUp

18

Dig In ConflictB

31

PTC Conflict

5

Analog in Loss

19

Dig In ConflictC

32

Brake Slipped

6

IntDBRes OvrHeat

20

Bipolar Conflict

33

AdjVoltRef Cflct

8

Drive OL Level 1

21

Motor Type Cflct

34

Home Not Set

9

Drive OL Level 2

22

NP Hz Conflict

38

DPI Port1 Loss

10

Decel Inhibt

23

MaxFreq Conflict

39

DPI Port2 Loss

11

Waking

24

VHz Neg Slope

40

DPI Port3 Loss

12

Motor Thermistor

25

IR Volts Range

49

Torq Prove Cflct

13

In Phase Loss

26

FluxAmpsRef Rang

50

Prof Step Cflct

14

Load Loss

27

Speed Ref Cflct

52

PI Config Conflict

Alarm

No

.

Ty

pe

(1)

Description

Advertising