Chapter 1

Programming and Parameters

Dynamic Control File

Fi

le

Grou

p

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Re

la

te

d

DYN

A

M

IC C

O

NTR

O

L

Ramp Ra

tes

140
141

[Accel Time 1]
[Accel Time 2]

Sets the rate of accel for all speed increases.

Default:

Min/Max:
Units:

10.0 Secs
10.0 Secs

0.0/3600.0 Secs
0.1 Secs

142
143
146
361

142
143

[Decel Time 1]
[Decel Time 2]

Sets the rate of decel for all speed decreases.

Default:

Min/Max:
Units:

10.0 Secs
10.0 Secs

0.0/3600.0 Secs
0.1 Secs

140
141
146
361

146 [S Curve %]

Sets the percentage of accel or decel time that is
applied to the ramp as S Curve. Time is added, 1/
2 at the beginning and 1/2 at the end of the
ramp.

Default:

Min/Max:
Units:

0%

0/100%
1%

140

143

Load Lim

its

147 [Current Lmt Sel]

Selects the source for the adjustment of current
limit (i.e. parameter, analog input, etc.).

Default:

Options:

0

0
1
2

“Cur Lim Val”

“Cur Lim Val”
“Analog In 1”
“Analog In 2”

146
149

148 [Current Lmt Val]

Defines the current limit value when [Current
Lmt Sel] = “Cur Lim Val.”
When in “Adj Voltage” mode, the output voltage
will not be allowed to exceed this value.

Default:

Min/Max:
Units:

[Rated Amps] x 1.5
(Equation yields approximate
default value.)

Based on Drive Rating
0.1 Amps

147
149

149 [Current Lmt Gain]

Sets the responsiveness of the current limit.

Default:

Min/Max:
Units:

250

0/5000
1

147
148

150 [Drive OL Mode]

Selects the drives response to increasing drive
temperature and can reduce the current limit
value as well as the PWM frequency. If the drive
is being used with a sine wave filter, the filter is
likely tuned to a specific carrier frequency. To
ensure stable operation it is recommended to set
this parameter to “Reduce CLim”

Default:

Options:

3

0
1
2
3

“Both–PWM 1st”

“Disabled”
“Reduce CLim”
“Reduce PWM”
“Both–PWM 1st”

219

151 [PWM Frequency]

Sets the carrier frequency for the PWM output.
Drive derating can occur at higher carrier
frequencies. For derating information, refer to
the PowerFlex Reference Manual.
Important: Changing the PWM frequency can
affect the motor lead length. Refer to the motor
cable length restriction tables in Wiring and
Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives, publication

DRIVES-IN001

.

Important: If parameter 053 [Motor Cntl Sel] is
set to “FVC Vector,” the drive will run at 2 kHz
when operating below 6 Hz.

Default:

Min/Max:
Units:

4 kHz
or 2 kHz
(Refer to

Appendix A

)

2/10 kHz
2/4/8/10 kHz

152 [Droop RPM @ FLA]

Selects amount of droop that the speed reference
is reduced when at full load torque. Zero disables
the droop function.
Important: Selecting “Slip Comp” with
parameter 080 in conjunction with parameter
152, can produce undesirable results.

Default:

Min/Max:
Units:

0.0 RPM

0.0/200.0 RPM
0.1 RPM

Max Speed

Accel Time

Accel Rate

=

Max Speed
Decel Time

Decel Rate

=